50Hz Mobile Generators
Operating the Machine
wc_tx000884gb.fm
25
MANUAL MAINS
With the control switch in this position:
The engine will not start even if the START
push button is pressed.
The microprocessor is programmed to
always use the mains as the supply for the
end consumer.
The mains contacts (CR) are closed.
The generator contacts (CG) are open.
MANUAL START
With the control switch in this position:
The engine will start when the START push
button is pressed.
The microprocessor is programmed to moni-
tor engine functions and generator output.
MANUAL GEN SET
With the control switch in this position:
The engine will not start even if the START
push button is pressed.
The microprocessor is programmed to
always use the generator as the supply for
the end consumer (utility).
The mains supply contacts (CR) are open.
The generator contacts (CG) are closed.
Position
Description
Summary of Contents for G 43
Page 1: ...Mobile Generator G 43 OPERATOR S MANUAL 0175257en 001 0608 0 1 7 5 2 5 7 E N...
Page 2: ......
Page 4: ...Foreword G 43 wc_tx000898gb fm 4...
Page 13: ...50Hz Mobile Generators Safety Information wc_si000271gb fm 13 Notes...
Page 18: ...Transporting Lifting and Storing 50Hz Mobile Generators wc_tx000895gb fm 18 Notes...
Page 48: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 48 5 Schematics 5 1 Power Wiring...
Page 50: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 50 5 3 Engine Wiring...
Page 52: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 52 5 5 Socket Wiring...
Page 54: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 54 5 7 Control Wiring...
Page 57: ...50Hz Mobile Generators Basic Troubleshooting wc_tx000896gb fm 57...
Page 60: ...Technical Data G 43 wc_td000277gb fm 60 7 3 Dimensions...
Page 62: ......
Page 64: ......