45
4.12 Checking/Adjusting Valve Clearances
Prerequisites
Engine off and cool
Cylinder head gasket
Feeler gauges
When
Every 1000 hours of service or yearly
Procedure
Follow the procedure below to check/adjust the valve clearances.
1. Turn the crankshaft until both valves in cylinder 1 overlap (exhaust valve about
to close, inlet valve about to open). Position 1 of diagram below.
2. Adjust the valves marked in black in position 1 of diagram.
3. Remove the cylinder head cover.
This procedure continues on the next page.