P118F Service Manual
START-UP AND OPERATION
1/6/09
5-4
! CAUTION !
If it should become necessary to add refrigerant to the system,
charging valve (28) is provided for this purpose. Be sure to follow
all local and federal regulations regarding the handling of
refrigerants and their illegal emission into the atmosphere.
! CAUTION !
Check the refrigerant level after the machine has operated for a few cycles. It should be slightly
above the minimum operating level, as indicated on the receiver, a few minutes prior to start of a
thawing period. If this level is low at this time, sufficient refrigerant should be added to the system
to raise the level above this point. Add only a small quantity (10 lbs. or less) at a time and operate
the machine several cycles to check the level before adding additional refrigerant. Refrigerant may
be added as a liquid through the charging valve (28) only while the machine is operating. It is
important that no air or other non-condensable gas enter the system when charging refrigerant into
the unit. It is also possible to check the refrigerant level by pumping machine down (See 9-11).
When the machine is pumped down, a liquid level should be observed in the gage glass on the
receiver.
Adding Refrigerant.
When adding refrigerant, it is necessary for the following procedure to be
followed:
1.
Make connection between charging valve and refrigerant cylinder using hose
or pipe suitable for R-22 or R-404a service. See instruction card attached to
refrigerant cylinder.
2.
Open valve on R-22 or R-404a cylinder and purge air out of charging line at
the charging valve connections.
3.
Open charging valve.
4.
Refrigerant can be added only during the freeze cycle. The charging valve
must be closed when the freezer is in a harvest.
In order to check the total charge in the system, it is necessary to transfer all of the refrigerant to the
receiver. A total pump down procedure should be performed.
See the name plate for the approximate refrigerant charge for the machine. Remember that the total
charge will vary for air-cooled machines with remote air-cooled condensers.
! DANGER !
Immediately close system charging valve at commencement of
defrost or thawing cycle if refrigerant cylinder is connected. Never
leave a refrigerant cylinder connected to system except during charging
operation. Failure to observe either of these precautions can result in
transferring refrigerant from the system to the refrigerant cylinder,
overfilling it, and possibly causing the cylinder to rupture because
of pressure from expansion of the liquid refrigerant.
! DANGER !
Summary of Contents for TUBE-ICE P-118F
Page 1: ...P 118F TUBE ICE MACHINE Service Manual 5000 1 6 09 ...
Page 4: ......
Page 6: ......
Page 14: ...P118F Service Manual INTRODUCTION 1 6 09 1 4 FIGURE 1 1 Assembly Air Cooled Front View ...
Page 15: ...P118F Service Manual INTRODUCTION 1 6 09 1 5 FIGURE 1 2 Assembly Air Cooled Rear View ...
Page 16: ...P118F Service Manual INTRODUCTION 1 6 09 1 6 FIGURE 1 3 Assembly Air Cooled Right Side View ...
Page 17: ...P118F Service Manual INTRODUCTION 1 6 09 1 7 FIGURE 1 4 Assembly Water Cooled Front View ...
Page 18: ...P118F Service Manual INTRODUCTION 1 6 09 1 8 FIGURE 1 5 Assembly Water Cooled Rear View ...
Page 19: ...P118F Service Manual INTRODUCTION 1 6 09 1 9 FIGURE 1 6 Assembly Water Cooled Right Side View ...
Page 20: ...P118F Service Manual INTRODUCTION 1 6 09 1 10 ...
Page 23: ...P118F Service Manual RECEIPT OF YOUR TUBE ICE MACHINE 1 6 09 2 3 ...
Page 37: ......
Page 38: ...1 6 09 ...
Page 48: ......
Page 49: ...1 6 09 ...
Page 88: ...P118F Service Manual SERVICE OPERATIONS 1 6 09 9 18 FIGURE 9 8 Cutter Water Tank Assembly ...
Page 89: ...P118F Service Manual SERVICE OPERATIONS 1 6 09 9 19 FIGURE 9 9 Cutter Tank Parts cylinder ice ...
Page 90: ...P118F Service Manual SERVICE OPERATIONS 1 6 09 9 20 FIGURE 9 10 Cutter Drive Parts ...
Page 102: ...P118F Service Manual TABLES CHARTS 1 6 09 11 1 11 Tables Charts ...
Page 111: ...P118F Service Manual TABLES CHARTS 1 6 09 11 10 ...