5-3
Add no more than 10 lb. (4.5 kg) of refrigerant and allow the machine to operate for several cycles before
checking the level again.
It is also possible to check the refrigerant level by pumping down the machine (Refer to
). When the
machine is pumped down, some liquid should be observed in the receiver’s sight glass.
Refrigerant must be added in liquid form through the machine
’s
charging valve. No air or other non-condensable
gases should enter the system when filling the machine with refrigerant. The compressor crankcase heater must
be energized for a minimum of two hours before starting and running the compressor.
While the machine is running, add refrigerant according to the steps below:
1.
Connect the charging valve on the machine to the refrigerant cylinder using a hose or pipe suitable for
R513A service. Refer to the instruction card attached to the refrigerant cylinder.
2.
Open the valve on the refrigerant cylinder and purge air out of the charging line at the charging valve
connection.
3.
Open the charging valve on the machine.
4.
The charging valve must be closed when the freezer is in a harvest period.
Immediately close the machine charging valve at the start of the harvest period if a refrigerant
cylinder is connected. Never leave a refrigerant cylinder connected to the system except during charging
operations. Failure to observe either of these precautions can result in transferring refrigerant from the system
into the refrigerant cylinder, causing it to overfill and possibly rupture as the liquid refrigerant expands.
Summary of Contents for Tube-Ice HFO10
Page 2: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 16: ...2 4 Figure 3 Water Cooled Piping Schematic ...
Page 17: ...2 5 Figure 4 Air Cooled Piping Schematic ...
Page 36: ......
Page 40: ......
Page 43: ...6 3 Figure 16 Panel Layout 60 Hz Non CE Machines ...
Page 44: ...6 4 Figure 17 Electrical Schematic Control Circuit All Voltages 50 Hz ...
Page 45: ...6 5 Figure 18 Electrical Schematic Control Circuit All Voltages 60 Hz ...
Page 46: ...6 6 Figure 19 Electrical Schematic 3 Phase Power All Voltages 50 Hz ...
Page 47: ...6 7 Figure 20 Electrical Schematic 3 Phase Power All Voltages 60 Hz ...
Page 68: ......
Page 96: ......
Page 110: ...Notes ...
Page 111: ...Notes ...