05TA Service Manual
TROUBLESHOOTING
8/13/01
8-9
SYMPTOM: High head pressure. (Water cooled machine)
POSSIBLE CAUSE
POSSIBLE REMEDY
Misadjusted or defective water regulating valve
Adjust or replace the valve. Never adjust the
valve stem as far open as it will turn, because it
will not close when the head pressure drops.
Insufficient water supply.
Check size of water line and pump output at
the condenser. Refer to the specification sheet
for water requirements. Check cooling tower
sump level and make-up water supply.
Cooling tower needs maintenance.
Check cooling tower fan belt and tighten or
replace as needed. Check spray nozzles and
sump screen and clean as needed.
Non-condensables (usually air) in system.
Check refrigerant tables for correct
pressure/temperature relation. If non-
condensables are present, Perform a total
pumpdown, let stand for at least 6 hours,
allowing non-condensables to gather in the
upper part of the receiver. Evacuate the
freezer and attach a recovery unit to the top
receiver purge valve (59). Open the valve and
recover the vapor for about five minutes.
When the freezer is evacuated, open the thaw
gas solenoid valve manually for about 15
seconds letting the top vapor in the receiver
blow into the freezer. Close the solenoid valve
and evacuate the freezer again. Evacuate to
500 microns and restart the machine.
Fouled (dirty) condenser.
Follow the diagnostic procedure outlined on
page 7-3, Section 7, and clean the condenser
per instructions under Condenser Cleaning,
Summary of Contents for TUBE-ICE 05TA
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 82: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 18 FIGURE 9 10 Cutter Drive Parts ...
Page 95: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 11 FIGURE 10 3 Control Panel Parts ...
Page 97: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 13 FIGURE 10 4 Wiring Schematic ...
Page 103: ...05TA Service Manual TABLES CHARTS 8 14 01 11 1 11 Tables Charts ...