![Vogt TUBE-ICE 05TA Service Manual Download Page 3](http://html.mh-extra.com/html/vogt/tube-ice-05ta/tube-ice-05ta_service-manual_1044457003.webp)
12/08/00
Warranty Registration / Start-Up Form
(Medium & Large Machines)
Model Number: __________________________
Serial Number: __________________________
This form must be filled out completely and signed by the customer in order to assure acceptance by Vogt.
Date of Start-Up:
_______________________________
Form Completed By: _____________________________________
AC Condenser Model Number: _____________________
AC Condenser Serial Number: _____________________________
Water Treatment System?
Yes
No
Manufacturer: ____________________
Model: ________________________
Bin Manufacturer: _______________________ Model: _________________________
Bin Capacity: _______ lbs.
Distributor
Company Name: ____________________________________________
Phone: _______________________
Address: ____________________________________ City: _________________________ State: ___________ Zip: ___________
Service Company
Company Name: ____________________________________________
Phone: _______________________
Address: ____________________________________ City: _________________________ State: ___________ Zip: ___________
Customer (location of equipment)
Company Name: ____________________________________________
Phone: _______________________
Address: ____________________________________ City: _________________________ State: ___________ Zip: ___________
PRE-OPERATION CHECK
Machine room suitable 50
°
F minimum, 110
°
F maximum
Power Supply ______ V _____ PH _____ HZ (machine not running)
Crankcase heater on for 2 hours minimum, prior to start
All valves opened or closed as tagged
Water supply and drains connected properly
Sufficient make-up water supply (minimum 30 PSIG)
Leak checked entire system (including AC condenser if applicable)
AC condenser cold weather temperature setting(s)
Solenoid ________ Fan________
AC condenser installed above machine
Yes
No
Approx. _____ft.
AC condenser line length (in equivalent feet) ____________
AC condenser properly piped — all lines insulated
Bin control(s) installed properly
Instruction manual and warranty certificate left on-site
Name of person left with: __________________________________
OPERATION CHECK
Power Supply ______ V _____ PH _____ HZ (machine running)
Compressor oil level, i.e. 1/4 – 1/2 – 3/4: ______
Compressor, pump , cutter & other motor direction of rotation correct
Compressor amps (Start of freeze cycle) L1_____ L2_____ L3_____
Cutter motor amps RLA__________ Actual __________
Water pump amps RLA__________ Actual __________
Condenser motor amps (if applicable) _________
Incoming potable water temperature: _____
°
F
All water distributors in place (visually inspected)
Make-up water float valve adjusted properly
Clear ice
Yes
No
Bin control(s) operate(s) properly to stop and start machine with ice
on them
Hour meter in control panel connected and operating
Suction Pressure: End of freeze ________ End of harvest ________
Discharge Pressure: End of freeze ________ End of harvest ________
Test
Cycle
Make-up Water
Temp
Freeze Time
Min/Sec
Harvest Time
Min/Sec
First Ice Out
Min/Sec
All Ice Out
Min/Sec
Avg. Hole
Size
Ice
Lb. Per Harvest
Ice
Lb. Per Day
#1
#2
#3
#4
Note: Ice lb. per day can be found by:
Remarks:
Technician Signature: ___________________________ End User Signature:_____________________________
I certify that I have performed all of the above procedures.
1440
×
+
me)
harvest ti
time
(freeze
harvest
per
lb.
ice
Tube Ice L.L.C.
1000 W. Ormsby
Louisville, KY 40210
(502) 635-3235
FAX #502-635-3024
THIS FORM MUST BE SENT TO
VOGT TO ACTIVATE WARRANTY
Vogt Order Number:
____________________
Summary of Contents for TUBE-ICE 05TA
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 82: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 18 FIGURE 9 10 Cutter Drive Parts ...
Page 95: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 11 FIGURE 10 3 Control Panel Parts ...
Page 97: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 13 FIGURE 10 4 Wiring Schematic ...
Page 103: ...05TA Service Manual TABLES CHARTS 8 14 01 11 1 11 Tables Charts ...