05TA Service Manual
TROUBLESHOOTING
8/13/01
8-7
SYMPTOM: Low compressor oil level.
POSSIBLE CAUSE
POSSIBLE REMEDY
Oil separator not returning oil.
Check oil separator float and oil return stop
valve (70) and line for a restriction. The oil
return line should be above ambient
temperature most of the time as it returns oil.
It may be cooler at the start of a freeze cycle.
Repair or replace defective parts.
Repeated short cycling (refrigerant carrying oil
out of compressor).
Usually caused by freeze-up, low refrigerant
charge, low head pressure, faulty timer, faulty
pressure switch or expansion valve clogged.
Use process of elimination.
Worn
piston
rings.
This condition is hard to detect without
dismantling the compressor and checking piston
ring tolerances. Normally there will be a little
puddle of oil laying on top of the piston when
the head and valve plate are removed. It is best
to replace the compressor.
Summary of Contents for TUBE-ICE 05TA
Page 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Page 82: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 18 FIGURE 9 10 Cutter Drive Parts ...
Page 95: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 11 FIGURE 10 3 Control Panel Parts ...
Page 97: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 13 FIGURE 10 4 Wiring Schematic ...
Page 103: ...05TA Service Manual TABLES CHARTS 8 14 01 11 1 11 Tables Charts ...