05TA Service Manual
TROUBLESHOOTING
8/13/01
8-10
SYMPTOM: High head pressure (Air-cooled machine).
POSSIBLE CAUSE
POSSIBLE REMEDY
Condenser fan(s) not running.
Defective motor, fan control switch, fan
contactor, or tripped circuit breaker in control
panel (CB2) Replace defective part. Check
condenser fan disconnect for thrown switch, or
blown fuse. Replace fuse and reset switch. If
the condenser is split, check the normally open
solenoid valve to make sure it is open, also
check the fan sequencing thermostats and fan
motor contactors to make sure they are
functioning properly. Replace any defective
parts.
Dirty condenser causing restricted airflow.
Visually inspect condenser and clean as
necessary.
Non-condensables (usually air) in the system.
Follow same procedure as specified for
removing non-condensables from Water
Cooled
machine
, except
evacuate the air-
cooled condenser also.