INSTALLING YOUR TUBE-ICE
®
MACHINE
8/13/01
3-11
Air-Cooled Condenser Wiring
FIGURE 3-7
Wiring For #DD-311 and #DD-361 Condenser
(3 phase motors)
Air-Cooled Connections
(See FIGURE 3-1 for connection sizes)
Follow these procedures to make a tight joint:
1. Silver solder or braze condenser tubing ends to the female Rota-lock connectors.
2. Remove dust caps if used, making sure that component plastic seals are intact.
3. Wipe off connector and spud threaded surfaces with a clean cloth to prevent the inclusion
of dirt or any foreign material in the system.
4. Connector coupling nut should be screwed onto Rota-lock spud using the proper amount
of torque.
Spud Size
Amount of Torque
7/8”
50-60 FT LBS
1 1/8”
80-100 FT LBS
1 3/8”
100-110 FT LBS
TABLE 3-6
Rota-lock Connector Torque Ratings