Drainage pipe installation
110
Installation
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
¾
Ensure at least 1/100 slope of the drainage pipe
¾
Adopt suitable pipe diameter
¾
Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
¾
Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
6.2.2 Drainage pipe selection
¾
The drainage pipe diameter shall not small than the drain hose of indoor unit
¾
According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu)
Water flowrate (l/h)
12
2.4
18
4
24
6
30
7
36
8
42
10
48
12
60
14
According to the above table to calculate the total water flowrate for the confluence pipe selection.
For horizontal drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate
(l/h)
Remark
Slope 1/50
Slope 1/100
PVC25
20
39
27
For branch pipe
PVC32
25
70
50
PVC40
31
125
88
Could be used for confluence pipe
PVC50
40
247
175
PVC63
51
473
334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate
(l/h)
Remark
PVC25
20
220
For branch pipe
PVC32
25
410
PVC40
31
730
Could be used for confluence pipe
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
Summary of Contents for ACP-12CC35AERI
Page 2: ......
Page 4: ......
Page 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Page 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Page 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Page 33: ...Wiring Diagrams Indoor Units 29 ...
Page 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Page 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Page 44: ...Service Space 40 Indoor Units 3 Service Space ...
Page 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Page 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Page 58: ...Features 54 Indoor Units ...
Page 60: ...Service Space 56 Indoor Units 3 Service Space ...
Page 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Page 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Page 70: ...Console Type 66 Console Type 3 Service Space ...
Page 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Page 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Page 77: ...Console Type Console Type 73 ...
Page 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Page 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Page 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Page 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Page 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Page 113: ...Refrigerant pipe installation Installation 109 ...
Page 176: ......
Page 177: ...ZZZ 9 9 FRP ...