Electrical Control Function
124
Electrical Control System
---T3<52
đ
, the compressor will not limit the frequency and resume to the former frequency.
---T3>60
đ
for 5 seconds, the compressor will stop until T3<52
đ
.
For other models: When T3>65
đ
for 3 seconds, the compressor will shut off. When T3
ψ
52,the compressor
will restart.
1.3.3 Heating Mode
1.3.2.1 Electronic Expansion Valve (EXV) Control
1.EXV will be fully closed when turning on the power. Then EXV will be standby with 300P open and will open
to target angle after compressor starts.
2.EXV will close with -160P when compressor stops. Then EXV will be standby with 300P open and will
open to target angle after compressor starts.
The unit is working in heating mode with the EXV open 300P(For 12K,it is 480P) for 3 minutes, then
adjusting EXV open angle according to the temperature of compressor discharge every 2 minutes.
1.3.3.2 Outdoor fan running rules:
7
(
'&B)$1B66/2:B63'B$''
'
'&B)$1B6/2:B63'B$''
&
'&B)$1B0,1B63'B$''
%
'&B)$1B0,'B63'B$''
$
'&B)$1B+,B63'B$''
ć
ć
ć
ć
ć
ć
ć
ć
$''
''
'
'
1.3.3.3 Indoor fan running rules:
For Console(12K):
In heating mode, indoor fan can be selected as high, medium, low, auto and silent. The anti-cold- wind
function has the priority.
When the compressor is running, the indoor fan is controlled as below:
Summary of Contents for ACP-12CC35AERI
Page 2: ......
Page 4: ......
Page 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Page 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Page 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Page 33: ...Wiring Diagrams Indoor Units 29 ...
Page 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Page 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Page 44: ...Service Space 40 Indoor Units 3 Service Space ...
Page 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Page 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Page 58: ...Features 54 Indoor Units ...
Page 60: ...Service Space 56 Indoor Units 3 Service Space ...
Page 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Page 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Page 70: ...Console Type 66 Console Type 3 Service Space ...
Page 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Page 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Page 77: ...Console Type Console Type 73 ...
Page 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Page 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Page 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Page 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Page 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Page 113: ...Refrigerant pipe installation Installation 109 ...
Page 176: ......
Page 177: ...ZZZ 9 9 FRP ...