Electrical Control Function
Electrical Control System
133
check function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
N
Display
Remark
00
Normal display
Display running frequency, running state or malfunction code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand is
15. the digital display tube show “60”,it means the capacity
demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator outlet temp.(heating T2
θ
cooling T2B)
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
d
isplay tube will show “70”.
07
Condenser pipe temp.(T3)
If the temp. is lower than -9 degree, the digital display tube will
show “
-
9”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected,
the digital display tube will
show: “
――
”
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the d
igital display tube will show “
13
”.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show “0.5”,it means the compressor discharge
temp. is 105 degree. the digital display tube show “1.6”,it
means the compressor discharge temp. is 116 degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
For example ,the digital display tube show “2.0”,it means the
EXV open angle is 120×4=480p.)
15
Frequency limit symbol
Bit7
Frequency limit
caused by IGBT
radiator
The display value is hex
number. For example,
the digital display tube
show 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit
caused by T4,T3 and
current.
Bit6
Frequency limit
caused by PFC
Bit5
Frequency limit
caused by T4.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2
Frequency limit
caused by T5.
Bit1
Frequency limit
caused by current
Bit0
Frequency limit
caused by voltage
16
DC fan motor speed
17
IGBT radiator temp.
The display value is between 30~120 degree. If the temp. is
lower than 30
degree, the digital display tube will show “
30
”.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display
tube show “0.5”,it means the
IGBT radiator temp. is
105 degree. the digital display tube show “1.6”,it means the
IGBT radiator temp. is 116 degree)
18
Indoor unit number
The indoor unit can communicate with outdoor unit well.
Summary of Contents for ACP-12CC35AERI
Page 2: ......
Page 4: ......
Page 16: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 19: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Page 20: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55Kφ φ Cooling Heating ...
Page 25: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Page 33: ...Wiring Diagrams Indoor Units 29 ...
Page 34: ...Static Pressure 30 Indoor Units 5 Static Pressure ACP 24DT70AERI ACP 36DT105AERI ...
Page 35: ...Static Pressure Indoor Units 31 ACP 42DT120AERI ACP 48DT140AERI ACP 55DT160AERI ...
Page 44: ...Service Space 40 Indoor Units 3 Service Space ...
Page 46: ...Wiring Diagrams 42 Indoor Units Pre setting Instructions ...
Page 55: ...Field Wiring Indoor Units 51 10 Field Wiring ...
Page 58: ...Features 54 Indoor Units ...
Page 60: ...Service Space 56 Indoor Units 3 Service Space ...
Page 61: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AERI ACP 18CC50AERI ...
Page 65: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AERI ACP 18CC50AERI ...
Page 70: ...Console Type 66 Console Type 3 Service Space ...
Page 71: ...Console Type Console Type 67 4 Wiring Diagrams ACP 12CT35AERI ...
Page 76: ...Console Type 72 Console Type 10 Field Wiring ACP 12CT35AERI ...
Page 77: ...Console Type Console Type 73 ...
Page 83: ...Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams ACP 12 CC CT 35AERI ACP 18 CC CF 50AERI ...
Page 84: ...Wiring Diagrams 80 Outdoor Units ACP 24 CC CF DT 70AERI ...
Page 85: ...Wiring Diagrams Outdoor Units 81 ACP 36 CC CF DT 105AERI ...
Page 86: ...Wiring Diagrams 82 Outdoor Units ACP 42 CC DT 120AERI ...
Page 87: ...Wiring Diagrams Outdoor Units 83 ACP 48 CC CF DT 140AERI ACP 55 CC CF DT 160AERI ...
Page 113: ...Refrigerant pipe installation Installation 109 ...
Page 176: ......
Page 177: ...ZZZ 9 9 FRP ...