Cabinet included with water drain tank with electric defrost
PREDISPOSED FOR REMOTE UNIT:
•
Monoblock unit: predisposed for remote unit.
•
Cabinet predisposed for remote unit.
Both of them include water pipe drain with siphon predisposed for water drain connection ( to be install by the
customer)
You never install the cabinet without siphon and to connect more drains of the same cabinet together.
Each drain must have only one siphon.
For more information please, see the APPENDIX 3 “VERSION”.
1.5 POSITIONING AND FEET REGULATION
Place the Cabinet in a perfect horizontal position, acting if necessary on the
screw type adjustable feet. Use a spirit level to check it. The Cabinet must be
placed in order to operate properly and allow the correct defrost condensate
water draining. In this way you will avoid noisy vibrations of the condensing
unit. Check the correct positioning of the condensate water basin and its
draining.
1.6 INSTALLATION INSIDE YOUR SHOP/RESTAURANT /WORKROOM
It is advisable to install the refrigerated table inside an area with an air conditioning system. Please note that
malfunctions may arise in areas that are not provided with air conditioning, e.g. condensation formation
The Cabinet with glass door are supplied with handle with screws to be
fi
xed by the customer. Install and
fi
x the
handle, put the bottom grid inside the cabinet.
ATTENTION
In order to allow a good functioning of the
Cabinet
please draw attentions to the following instructions:
•
Do not place the cabinet to a direct exposure of sunlight and to all the other means of irra-
diation,
such as high intensity incandescent lights, cooking ovens, heating radiators.
•
Avoid to close the air in-take
of the monoblock or built-in unit.
•
Do not put any material as carton or others, on the top of the cabinet
in which is positioning the
monoblock unit or the condensing unit.
•
Do not positioning the cabinet inside the area in which there is to much humidity
(possible
making condensation of the surface of the cabinet).
•
Do not positioning the cabinet inside a close cavity
(there is no circulation of air and the cabinet
will not run properly).
•
Do not positioning two or more cabinets back-to-back position
(the unit will not be properly).
Verify that in the installation room there is enough air turnover, even during closing and rest hours. In
this way the expansion/condensing unit will work correctly.
Summary of Contents for 400 L
Page 93: ...ARABIC 92 2004 108 CE 2006 95 CE 2002 95 EC RoHS...
Page 95: ...ARABIC 94 1 Kg 1 1 8 2 1 4...
Page 96: ...95 ARABIC 3 1 4 1 3 5 1 2 6 1...
Page 97: ...ARABIC 96 1 7 400 L 600 L 700 L 1200 L 1400 L 400 L 600 L 700 L 900 L 1200 L 1400 L...
Page 98: ...97 ARABIC 8 1 9 1 2 1 2 30 3 1 2 10 6 2 3 3 30 4 2 5 6...
Page 99: ...ARABIC 98 2 2 x x x x 8 x x 2 1 0 OFF x 2 1 1 ON...
Page 100: ...99 ARABIC 3 1 3 3 2...
Page 101: ...ARABIC 100 4 1 4 40 2 4 4 3 18...
Page 102: ...101 ARABIC...
Page 103: ...ARABIC 102 5 1 5 5 2 90 5 3 4 5 5 5 3 2 6 5...
Page 104: ...103 ARABIC 7 5 8 5...
Page 143: ...IT EN F DE ES ARABIC Appendici Manuale d uso e manutenzione 142 Note...
Page 144: ...Appendici Manuale d uso e manutenzione IT EN F DE ES ARABIC 143 Note...