Event-ID
Description
0xEA51
Error - There is no PROFINET IO controller at the configured slot
ZInfo1: User slot of the PROFINET I/O controller
ZInfo2: Recognized ID at the configured slot
0xEA53
Error - PROFINET configuration - There are too many PROFINET IO
devices configured
ZInfo1: Number of configured devices
ZInfo2: Slot
ZInfo3: Maximum possible number of devices
0xEA54
Error - PROFINET IO controller reports multiple parametrization of a
periphery address
ZInfo1: Periphery address
ZInfo2: User slot of the PROFINET I/O controller
ZInfo3: Data width
0xEA61 ... 0xEA63 Internal error - Please contact the VIPA Hotline!
0xEA64
PROFINET/EtherCAT CP
Configuration error: Zinfo1:
Bit 0: Too many devices
Bit 1: Too many devices per ms
Bit 2: Too many input bytes per ms
Bit 3: Too many output bytes per ms
Bit 4: Too many input bytes per device
Bit 5: Too many output bytes per device
Bit 6: Too many productive connections
Bit 7: Too many input bytes in the process image
Bit 8: Too many output bytes in the process image
Bit 9: Configuration not available
Bit 10: Configuration not valid
Bit 11: Cycle time too small
Bit 12: Cycle time too big
Bit 13: Not valid device number
Bit 14: CPU is configured as I device
Bit 15: Obtain an IP address in a different way is not supported for the IP
address of the controller
0xEA65
Internal error - Please contact the VIPA Hotline!
VIPA System 300S
Deployment CPU 313-6CF13
VIPA specific diagnostic entries
HB140 | CPU-SC | 313-6CF13 | GB | 15-50