Event-ID
Description
0xE8FB
CMD - Auto command: Error: Initialization of the Ethernet PG/OP channel
by means of SET_NETWORK is faulty
0xE8FC
CMD - Auto command: Error: Some IP parameters missing in SET_NET-
WORK
0xE8FE
CMD - Auto command: Error: CMD_START missing
0xE8FF
CMD - Auto command: Error: Error while reading CMD file (memory card
error)
0xE901
Check sum error
0xEA00
Internal error - Please contact the VIPA Hotline!
0xEA01
Internal error - Please contact the VIPA Hotline!
0xEA02
SBUS: Internal error (internal plugged sub module not recognized)
ZInfo1: Internal slot
0xEA03
SBUS: Communication error CPU - PROFINET I/O controller:
ZInfo1: Slot
ZInfo2: Status
(0: OK, 1: ERROR, 2: BUSY, 3: TIMEOUT, 4: LOCKED, 5: UNKNOWN)
0xEA04
SBUS: Multiple parametrization of a periphery address
ZInfo1: Periphery address
ZInfo2: Slot
ZInfo3: Data width
0xEA05
Internal error - Please contact the VIPA Hotline!
0xEA07
Internal error - Please contact the VIPA Hotline!
0xEA08
SBUS: Parametrized input data width unequal to plugged input data width
ZInfo1: Parametrized input data width
ZInfo2: Slot
ZInfo3: Input data width of the plugged module
0xEA09
SBUS: Parametrized output data width unequal to plugged output data width
ZInfo1: Parametrized output data width
ZInfo2: Slot
ZInfo3: Output data width of the plugged module
0xEA10
SBUS: Input periphery address outside the periphery area
ZInfo1: Periphery address
ZInfo2: Slot
ZInfo3: Data width
VIPA System 300S
Deployment CPU 313-6CF13
VIPA specific diagnostic entries
HB140 | CPU-SC | 313-6CF13 | GB | 15-50
83