The deployment of the request interface takes place at the following
sequence:
1.
Edit the following input parameters:
Name
Data type
Address (DB) Default
Comment
JOB_REQ
BOOL
4.3
FALSE
Initiates the job (edges 0-1) *
JOB_ID
WORD
6.0
0
Job ID:
00h Job without function
01h Writes the count value
02h Writes the load value
04h Writes the comparison
value
08h Writes the hysteresis
10h Writes the pulse duration
20h Writes the end value
82h Reads the load value
84h Reads the comparison
value
88h Reads the hysteresis
90h Reads the pulse duration
A0h Reads the end value
JOB_VAL
DINT
8.0
0
Value for write jobs
*) State remains set also after a CPU STOP-RUN transition.
2.
Call the SFB. The job is processed immediately.
JOB_DONE
only applies to SFB run with the result FALSE.
JOB_ERR
=
TRUE if an error occurred. Details on the error cause are indi-
cated at
JOB_STAT
.
Name
Data type
Address (DB) Default
Comment
JOB_DONE
BOOL
22.0
TRUE
New job can be started
JOB_ERR
BOOL
22.1
FALSE
Job error
JOB_STAT
WORD
24.0
0000h
Job error ID
0000h No error
0121h Compare value too low
0122h Compare value too high
0131h Hysteresis too low
0132h Hysteresis too high
0141h Pulse duration too low
0142h Pulse duration too high
0151h Load value too low
0152h Load value too high
0161h Count value too low
0162h Count value too high
01FFh Invalid job ID
Proceeding
VIPA System 300S
Deployment I/O periphery
Counter > SFB 47 - COUNT - Counter controlling
HB140 | CPU-SC | 313-6CF13 | GB | 15-50