Order no.
313-6CF13
Technical data digital inputs
Number of inputs
16
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load
voltage
ü
Current consumption from load voltage L+
(without load)
70 mA
Rated value
DC 24 V
Input voltage for signal "0"
DC 0...5 V
Input voltage for signal "1"
DC 15...28.8 V
Input voltage hysteresis
-
Frequency range
-
Input resistance
-
Input current for signal "1"
6 mA
Connection of Two-Wire-BEROs possible
ü
Max. permissible BERO quiescent current
1.5 mA
Input delay of "0" to "1"
0.1 / 0.35 ms
Input delay of "1" to "0"
0.1 / 0.35 ms
Number of simultaneously utilizable inputs hori-
zontal configuration
16
Number of simultaneously utilizable inputs ver-
tical configuration
16
Input characteristic curve
IEC 61131-2, type 1
Initial data size
2 Byte
Technical data digital outputs
Number of outputs
16
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load
voltage
-
Current consumption from load voltage L+
(without load)
100 mA
Total current per group, horizontal configura-
tion, 40°C
3 A
Total current per group, horizontal configura-
tion, 60°C
2 A
VIPA System 300S
Hardware description
Technical data
HB140 | CPU-SC | 313-6CF13 | GB | 15-50
36