Chapter 5 Deployment Command interface
Manual VIPA System 300V
5-4
HB130E - CP - RE_343-2AH10 - Rev. 08/41
DONE
ERROR
STATUS Meaning
1 0
0000h
Job is complete without error
0
1
8090h
Address in LADDR invalid
0
1
8092h
A type other than BYTE is specified in the ANY reference
0
1
8093h
This SFC is not permitted fort he modules selected with
LADDR and IOID.
0
1
80A0h
Negative acknowledgment when reading from AS-i
master
0
1
80A1h
Negative acknowledgment when writing to AS-i master
0
1
80A2h
DP protocol error at layer 2
0
1
80A3h
DP protocol error at user interface/user
0
1
80A4h
Communication problems on bus
0
1
80B0h
AS-i master does not recognize the data record
0
1
80B1h
Specified data record length incorrect
0
1
80B2h
The configured slot is not use.
0
1
80B3h
Actual module type does not match the expected module
type in SDB1
0
1
80C0h
Data record cannot be read
0
1
80C1h
The specified data record is currently being processed
0
1
80C2h
There is a job pileup.
0
1
80C3h
Resource (memory) in use
0 1
80C4h
Communication
error
0
1
80C5h
Distributed I/Os not available
0
1
80C6h
Data record transfer aborted due to priority class abort
(warm restart or background) of the distributed I/Os.
0 1
8181h
Job active (no error)
0 1
8182h
ID from block execution with STARTUP=TRUE
(not an error)
0
1
8184h
Data type of the RECV formal parameter illegal
0
1
8381h
The AS-i slave address is incorrect.
0
1
8382h
The AS-i slave is not activated (not in LAS).
0
1
8383h
Error on the AS interface.
0
1
8384h
Command not permitted in the current status of the AS-i
master.
0
1
8385h
An AS-i slave with address 0 exists.
0
1
8386h
The AS-i slave has illegal Configuration data (I/O or ID-
Codes
).
0
1
83A1h
The addressed AS-i slave was not found on the AS
interface.
0
1
83A2h
An AS-i slave with address 0 exists.
0
1
83A3h
An AS-i slave with the new address already exists on the
AS-Interface.
0
1
83A4h
The AS-i slave address cannot be deleted.
0
1
83A5h
The AS-i slave address cannot be set.
0
1
83A6h
The AS-i slave address cannot be stored permanently.
0
1
83A7h
Error reading the extended ID1 code
0
1
83A8h
The target address is not plausible (for example a B
slave address was used for a standard slave).
continued ...