Manual VIPA System 300V
Chapter 4 Deployment CP 343-2P ASI
HB130E - CP - RE_343-2AH10 - Rev. 08/41
4-15
In the following there is an extract (local byte 8...11) from the record set 0
of the OB 82.
Local byte Bit Variable
Data
type
Description
8
0 OB82_MDL_DEFECT
BOOL
Group error bit
0: Interrupt going
1: Interrupt incoming
1 OB82_INT_FAULT
BOOL
Internal error e.g. Flash-ROM defective
2 OB82_EXT_FAULT
BOOL
External error e.g. slave failed or APF
3 OB82_PNT_INFO
BOOL
At least one slave differs from the
expected configuration
4 OB82_EXT_VOLTAGE
BOOL
Voltage on the AS-interface to low
(APF)
5 OB82_FLD_CONNCTR
BOOL
with the CP always 0
6 OB82_NO_CONFIG
BOOL
with the CP always 0
7 OB82_CONFIG_ERR
BOOL
with the CP always 0
9
OB82_MDL_TYPE
BYTE
Module class: for CP: 1Ch
10
0 OB82_SUB_MDL_ERR
BOOL
At least 1 slave differs from the
expected configuration
1 OB82_COMM_FAULT
BOOL
with the CP always 0
2
OB82_MDL_STOP BOOL
Operating
mode
0: CP is in normal state
1: CP is offline
3 OB82_WTCH_DOG_FLT
BOOL
Hardware error of the CP
(internal watchdog)
4 OB82_INT_PS_FLT
BOOL
with the CP always 0
5 OB82_PRIM_BATT_FLT
BOOL
with the CP always 0
6 OB82_BCKUP_BATT_FLT BOOL
with the CP always 0
7 OB82_RESERVED_2
BOOL
with the CP always 0
11
0 OB82_RACK_FLT
BOOL
with the CP always 0
1 OB82_PROC_FLT
BOOL
with the CP always 0
2
OB82_EPROM_FLT BOOL
Flash-ROM
defective
3 OB82_RAM_FLT
BOOL
with the CP always 0
4 OB82_ADU_FLT
BOOL
with the CP always 0
5 OB82_FUSE_FLT
BOOL
with the CP always 0
6 OB82_RESERVED_3
BOOL
with the CP always 0
Local data OB 82
record set 0