Chapter 5 Deployment Command interface
Manual VIPA System 300V
5-8
HB130E - CP - RE_343-2AH10 - Rev. 08/41
Set_Permanent_Parameter
With this call a parameter value for the specified AS-i slave is configured on
the CP. The value is stored permanently in the Flash-ROM of the CP.
The configured parameter is
not
transferred immediately by the CP to the
AS-i slave. The configured parameter value is only transferred when the
AS-i slave is activated after turning on the power supply on the CP.
This call is not permitted for AS-i slaves that comply with the AS-i slave
standard profile 7.4. For these AS-i slaves, the AS-i master handles the AS-
i slave parameter assignment itself. In this case, the configured parameters
are always set to Fh.
Attention!
If you configure the AS-i slaves with a hardware configuration, using the
call described here is generally unnecessary.
If you use the call, you will overwrite the corresponding configuration data
originating from the button configuration or the configuration set with
hardware configuration.
Structure of the Job Data in the Send buffer
Meaning
Byte
Bit 7 Bit 4 Bit 3 Bit 0
0
Command number: 00h
1 Slave
address
2 irrelevant
Parameter
Get_Permanent_Parameter
With this call, a slave-specific parameter value stored on the Flash-ROM of
the CP is read.
Structure of the Job Data in the Send buffer
Byte
Meaning
0
Command number: 01h
1 Slave
address
Structure of the Job Data in the Receive buffer
Meaning
Byte
Bit 7 Bit 4 Bit 3 Bit 0
0 reserved configured
parameters
Description
Description