Hardware configuration
The description here refers to modules that are at the same bus together
with the CPU. In order to address the installed peripheral modules
individually, specific addresses in the CPU have to be assigned to them.
The allocation of addresses and the configuration of the installed modules
is a function of the Siemens SIMATIC manager.
Here navigate within the hardware catalog to the according CP and place it
at the S7-300 station.
After the CP is inserted, there is still no AS-i slave configured. Here there is
the possibility for "button configuration". The current configuration may be
stored by the "button configuration"
Note!
Please regard a configuration produced respectively modified by the
Siemens SIMATIC manager always has priority in relation to a button
configuration! At start-up of the CPU the CP gets its AS-i configuration
from the CPU. Here a possibly existing button configuration is overwritten.
•
Start the Siemens SIMATIC Manager.
•
Swap to the hardware configurator.
•
Place a profile rail via drag&drop from the hardware catalog to the
project window.
•
Project the CPU and the corresponding modules. Place the corres-
ponding modules via drag&drop from the hardware catalog to the
corresponding slot of the profile rail.
•
To project the VIPA CP 343 the Siemens CP 343-2P (6GK7 343-
2AH10-0XA0) at the according slot is to be used.
•
Save and translate your project and transfer it to the CPU.
•
Execute a button configuration (see "Button configuration")
•
Upload the current configuration into the PG (see "Upload current
configuration to PG").
•
The current configuration may be checked respectively modified by the
properties of the CP 343-2P. More information about the configuration of
an AS-i slave may be found at the same named part in this chapter.
Overview
Project
engineering