background image

 

-18- 

 

 

 

 

4) Alarm Signals 

 

The alarm codes are described as follows. 

 

MESSAGE 

CAUSE 

FUNCTION 

P1 

Temperature probe 

faulty 

Compressor switching to Con and CoF 

HA 

High temperature 

alarm 

Probe temperature ALU higher than the setting 
temperature; Outputs unchanged 

LA 

Low temperature alarm 

Probe temperature ALL lower than the 

setting temperature; Outputs unchanged 

CA 

External alarm 

All outputs off 

 

Probe alarms P1”, start a  few seconds after  the fault in  the related probe; they 
automatically stop a few seconds after the probe restarts normal  operation. Check 
connections  before  replacing  the  probe.  Temperature  alarms  “HA”,  “LA” 
automatically  stops  as  soon  as  the  temperature  returns  to  normal  value.  Alarm 
“CA” (with i1F=PAL) recovers only by switching off and on the instrument. 

 

2.  Temperature Setting 

 

  Set the temperature at 55 

°

for the optimum aging of wine 

  On  initial  start-up,  the  time  required  to  reach  the  desired  temperature  will vary, 

depending  on  the  quantity  of  bottles,  temperature  setting  and surrounding 
temperature. 

  Allow  24  hours  to  stabilize  the  temperature  for  each  new  temperature  setting 

operation 

 

3. How to see temperature set-point 

 

1) Press and immediately release the 

SET 

key, the display will show the set-point 

value. 
2) Press again and immediately release the 

SET 

key to display the probe value. 

 

4. How to change the set-point 

 

1)  Press and hold the 

SET 

key until the 

“°C” or “°F” LED starts flashing and the 

set-point is displayed. 
2) Press the up/down keys 

to change the set-point value within 10 sec. 

3) Press the 

SET 

key again to store the new set-point value. 

NOTE

: The unit turns on at set-point 

Set 

plus regulation differential 

Hy 

after anti- 

short cycle 

AC 

has elapsed; the unit turns off at set-point 

Set

 

5. Manual Defrost 

Press and hold the defrost 

 key until defrost starts. The defrost indicator will be 

on. 

Summary of Contents for WINE-MATE WM-1500HZD

Page 1: ...www winemate com Wine Cooling System WM 1500HZD WM 2500HZD WM 3500HZD WM 4500HZD WM 6500HZD WM 8500HZD Installation Use Care Manual www vinotemp com Read and save these instructions ...

Page 2: ...ce with the National Electrical Code ANSI NFPA 70 latest edition and local codes and ordinances It is the personal responsibility of the consumer to have a proper 3 prong wall receptacle installed by a qualified electrician DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE POWER CORD GROUNDING PRONG A separate adequately fused and grounded circuit should be available for this appliance Do not remove any g...

Page 3: ... 2 ELECTRICAL SHOCK HAZARD Disconnect electrical supply from appliance before servicing Replace all panels before operating Failure to do so could result in death or electrical shock ...

Page 4: ... 3 Table of Contents Features Specifications 3 Installation Instructions 6 Temperature Humidity 16 Care Guide 20 Troubleshooting 21 Electrical Diagrams 24 Customer Support 26 Warranty 27 ...

Page 5: ...ain humidity ranges within 50 70 RH o These temperature and humidity ranges are optimized for long term storage of wine o Temperature is controlled and humidity is adjusted using innovative technology o Horizontal cold air supply is optimized for use in the wide cabinets or wine rooms o The unit is self contained ready for easy installation and use Fig 1 1 WM 1500 2500HZD FEATURE DESCRIPTIONS ...

Page 6: ... 5 Fig 1 2 WM 3500 8500HZD FEATURE DESCRIPTIONS Fig 1 3 WM 1500 2500HZD DIMENSIONS ...

Page 7: ...frequency and current specified on the label at the cooling unit The rated capacity is determined under the cellar and ambienttemperatures of 55 F and 75 F with R13 interior and R19 exterior insulations Any lower cellar temperature higher ambient temperature and less insulation will cause reducing capacity and may not maintain 55 F The ambient temperatures for WM 1500HZD shall not be higher than78...

Page 8: ...nd a 3 slot receptacle that will plug into the appliance The marked rating of the extension cord shall be 115 V 15 A or equivalent for WM 1500 2500HZD and 115 V 20 A or equivalent for WM 3500 8500HZD and not greater than 15ft in length 1 General Instructions The cooling unit produces cooling supplied into the cellar meanwhile it also generates heat that must be exhausted outside the cellar So the ...

Page 9: ...1 4 ID wood thread inserts at the ceiling see Fig 2 1 2 2 Place the gaskets 1 2 foam tape on the mounting lip sides see Fig 2 3 If top exhaust installation place another gaskets along the top exhaust at thetop of the cooling unit see Fig 2 4 Move the cooling unit towards the mounting sides and push to press the gaskets see Fig 2 5 Use 2 brackets and screws with 7 16 wrench to secure the cooling un...

Page 10: ... 9 Fig 2 2 THREAD INSERT Fig 2 3 REAR GASKET ...

Page 11: ... 10 Fig 2 4 TOP EXHAUST GASKET Fig 2 5 COOLING UNIT MOUNTING ...

Page 12: ... 11 Fig 2 6 SECURING BRACKET SCREW ...

Page 13: ... 12 Fig 2 7 CABINET GRILLE ...

Page 14: ... Construct a shelf as shown The shelf must be capable of supporting the weight of the cooling unit and preventing it from moving Place the cooling unit on the shelf with the back of the unit flush with the outside of the wall Seal the clearance between the cooling unit and opening with a high quality weather stripping polyurethane spray foam or foam tape Cover the seal with molding and attach the ...

Page 15: ...an be installed with the front of the unit flush with the inside of the wall Construct a shelf outside the room accordingly Fig 2 9 THROUGH WALL INSTALLATION OUTSIDE WALL FLUSH Fig 2 10 THROUGH WALL INSTALLATION INSIDE WALL FLUSH ...

Page 16: ...m of R13 insulation All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation The vapor barrier shall be installed on the warm side of the insulation All joints door frames electrical outlets or switches and any pipes or vents that go through the cellar shall be sealed to prevent air and moisture leakage into the cellar Concrete rock and brick are not insulation or ...

Page 17: ...ll not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduced to the cellar Symptoms of this condition are cooling unit runs all the time with only a slight reduction in temperature and or water overflows from the unit Because of the temperature difference between the inside and outside very small cracks can allow large amounts of outside air to enter...

Page 18: ...ck the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys press up down keys until PON is displayed 3 Display During normal operating conditions the display shows the value measured by the air temperature probe In case of active alarm the temperature flashes al...

Page 19: ...re at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature willvary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new temperature setting operation 3 How to see temperature set point 1 Press and immediately release the SET key the display will show the se...

Page 20: ... temperature unit F C F Fahrenheit rES display resolution in integer dLy temperature display delay min 1 ot probe calibration 0 LS minimum set point 50 US maximum set point 65 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative to set point ALU high temperature alarm 10 ALL low temperature alarm 10 AFH alarm recovery differential 5...

Page 21: ...e will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 11 How to set low cellar temperature heater The heater turns on at SAA minus Shy the heater turns off at SAA NOTES Use a forced air heater to warm up the wine cellar If there is a thermost...

Page 22: ...te if it is accumulated on the cooling unit in high humidity conditions 3 Removing Unit When you remove the cooling unit beware water may come out of the unit 4 Installing Drain Line WM 3500 8500HZD units are equipped with an additional drain fitting In case of extreme humidity there is a drain line needed remove the drain plug on the bottom left at the rear then remove the connection plug and fit...

Page 23: ...e is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost cycle and turns off at 55 F of air temperature The average air temperature is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change so quickly...

Page 24: ...for excessive size c Check for installation location d Leave minimum 3 feet clearance for the hot air exhaust side and leave minimum 1 foot clearance for the fresh air intake side e Clean condenser f Check for fan and air short circulation 8 Fan motor running but compressornot running a Post compressor fan runningmode b Incorrect or loose wirings c Failed components d Liquid refrigerant in t hecom...

Page 25: ... 23 12 Temperature a Low temperature setting a Raise the setting ...

Page 26: ...ing excessivecondensate c Evaporator air flow restriction d Water passages restricted e Drip tray leak No water overflowbut water leak a Check for air leak b Use drain line c Check supply air flow or air TD d Clean the drip tray e Seal the leak using silicone sealant 15 Excessive condensatein wine cellar a Air leak in the wine cellar causingexcessive condensate b High humidity causing excessivecon...

Page 27: ... 25 Electrical Wiring Diagrams Fig 6 1 WM 1500 2500HZD WIRING DIAGRAM Fig 6 2 WM 1500 2500HZD WIRING DIAGRAM ALARM CALL ...

Page 28: ... 26 Fig 6 3 WM 3500 8500HZD WIRING DIAGRAM Fig 6 4 WM 3500 8500HZD WIRING DIAGRAM ALARM CALL ...

Page 29: ... 27 Customer Support If you need further assistance please contact us at Vinotemp International 732 South Racetrack Road Henderson NV 89015 Tel 800 777 8466 Fax 310 886 3310 Email info vinotemp com ...

Page 30: ...plied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the continental UNITED STATES only VINOTEMP cooling units are warranted to produce the stated number of BTU H While every eff...

Page 31: ... BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its units to properly cool a particular enclosure Customers are cautioned that enclosure construction unit location and many other factors can affect the operation and performance of the unit There for suitability of t...

Reviews: