6. Parameter Programming
1) Press and hold the
SET
+
keys until the “
°C” or “°F”
LED starts flashing,
then release the keys.
2) Press and hold again the
SET
+
keys until the
Pr2
label is displayed, then
release the keys. The first parameter
Hy
will be displayed.
3) Press up/down keys /
to scroll to the required parameter within 10 sec.
4) Press the
“
SET
” key to display its value.
5) Use up/down keys
to change its value within 10 sec.
6) Press
“
SET
” to store the new value and the display will flash 3 times.
7)
To exit
: Press
SET +
or wait 15sec without pressing a key.
PARAMETER
DESCRIPTION
DEFAULT VALUE
Set
set-point (
°
)
55
Hy
temperature regulation differential
(
°
)
4
AC
anti-short cycle delay (min)
10
Con
compress on with probe faulty (min)
15
CoF
compress off with probe faulty (min)
30
CF
temperature unit
(
°
F
/ °
C
)
F: Fahrenheit
rES
display resolution
in: integer
dLy
temperature display delay (min)
1
ot
probe calibration
(
°
)
0
LS
minimum set-point
(
°
)
50
US
maximum set-point
(
°
)
65
idF
defrost cycle interval time (hour)
12
MdF
defrost cycle endurance time (min)
30
ALC
temperature alarm type
rE: relative to set-point
ALU
high temperature alarm
(
°
)
10
ALL
low temperature alarm
(
°
)
10
AFH
alarm recovery differential
(
°
)
5
ALd
temperature alarm delay (min)
60
dAO
temperature alarm delay on startup (hr)
23
SAA
heater set-point
(
°
)
40
SHy
heater regulation differential
(
°
)
4
FSU
fan action
Std
FnC
fan operating mode
C-n: on with compressor & off
during defrost
Fon
fan on with compressor off (min)
0
FoF
fan off with compressor off (min)
15
NOTE
: Depending on the controller, not all parameters are used.
7. How to calibrate the air probe
If the actual cellar temperature differs from the setting temperature, set
parameter
ot
= actual cellar temperature minus set-point.
8. How to adjust defrost cycle
Summary of Contents for WINE-MATE WM-1500HZD
Page 6: ... 5 Fig 1 2 WM 3500 8500HZD FEATURE DESCRIPTIONS Fig 1 3 WM 1500 2500HZD DIMENSIONS ...
Page 10: ... 9 Fig 2 2 THREAD INSERT Fig 2 3 REAR GASKET ...
Page 11: ... 10 Fig 2 4 TOP EXHAUST GASKET Fig 2 5 COOLING UNIT MOUNTING ...
Page 12: ... 11 Fig 2 6 SECURING BRACKET SCREW ...
Page 13: ... 12 Fig 2 7 CABINET GRILLE ...
Page 25: ... 23 12 Temperature a Low temperature setting a Raise the setting ...
Page 28: ... 26 Fig 6 3 WM 3500 8500HZD WIRING DIAGRAM Fig 6 4 WM 3500 8500HZD WIRING DIAGRAM ALARM CALL ...