51
Parameter
Parameter group
Display
53:...
General
Connection at plug 20A1
54:...
General
Connection at plug 29
55:...
General
Connection at plug 52A1
98:...
General
Viessmann system number
9C:...
General
LON subscriber monitoring
0C:...
Boiler
Function butterfly valve
Note
For overview of all parameters: See from page 56
Adjust control unit to 2-stage burner
0
1.
Start the burner.
0
2. Tap the following buttons:
0
3. "Service"
0
4.
Enter the password "viservice".
0
5. "Actuator test"
0
6. "Burner stage 2"
0
7.
Determine the maximum burner output by means
of the fuel consumption.
Record the relevant value.
0
8. "Burner stage 1"
0
9.
Determine the minimum burner output (base load)
through the fuel consumption.
Record the relevant value.
10.
Use
to end the actuator test.
11.
Set the values determined in parameter level 2 in
the
"Boiler"
group: See the following table.
Parameter
Display
Setting
02:...
Burner type
1 = 2-stage
2 = modulating
03:...
Boiler protection, gas/oil operation
0 = gas operation
1 = oil operation
08:...
Maximum burner output in kW
1 step
≙
1 kW
Units and tens of the determined maximum out-
put
Example:
Max. output = 225 kW
Here set = 25
09:...
Maximum burner output in 100 kW
1 step
≙
100 kW
Hundreds of the determined maximum output
Example:
Max. output = 225 kW
Here set = 2
0A:...
Burner base load
Ratio of burner stage 1 output to maximum rat-
ed output
Standard output adjustable from 15 to 100 % of
max. rated output
Commissioning
Required parameters
(cont.)