64
57 Run-on time, shunt pump, boiler circuit pump or distribution pump
Display
Value
Explanations
Run-on time for circulation pump on plug
sL
Note
Connection to distribution pump not possible
5 min
57:5
None
57:0
... min
57:1 to
57:60
76 Communication module
Display
Value
Explanations
Without
76:0
With
76:1
Recognised automatically.
77 LON subscriber number
!
Display
Value
Explanations
Displayed only if parameter "76:1" has been set.
Note
Each number can only be assigned once.
...
77:1
to
77:8
Boiler
9
77:9
Cascade
...
77:10 to
77:96
Vitotronic 200-H
97
77:97
Vitogate 300, type BN/MB
98
77:98
Vitogate 200, type KNX
99
77:99
Vitocom 300, type LAN3
or
Vitocom 100, type LAN1
78 Communication LON
Display
Value
Explanations
Displayed only if parameter "76:1" has been set.
Disabled
78:0
Enabled
78:1
Parameter
General
(cont.)
5863679
Parameter
Summary of Contents for Vitotronic 11 CC1E