Rated voltage
230 V~
Rated current
Max. 4(2) A~
Connecting an AC burner
Pressure-jet oil/gas burner
■
The burner cables are included in the standard boiler
delivery.
■
Connect burner to
DIN 4791
.
■
Max. power consumption 6 (3) A
41
L
B4
S3
T2
T1
N
41
Störung H1
BZ
N
PE
L1
STB
TR
L1
N T1 T2 S3 B4
Fig. 17
A
To the control unit
B
To the burner
Plug terminal designations
fA
:
L1
Phase via high limit safety cut-out to the burner
PE
Earth conductor to burner
N
Neutral conductor to burner
T1, T2 Control chain
S3
Burner fault terminal
B4
Hours run meter terminal
Signal flow direction:
Control unit
→
burner
Signal flow direction:
Burner
→
control unit
Plug equipment codes
fA
:
STB Control unit high limit safety cut-out
TR
Control unit temperature controller
H1
Burner fault signal
BZ
Hours run meter
BN
BK
BU
90
T7T8
T6
Fig. 18
A
To the control unit
B
To the burner
Plug terminal designations
lÖ
:
T6, T8 Control chain burner stage 2 ON or modulation
controller Open
T6, T7 Control chain burner stage 2 OFF or modula-
tion controller Close
Electrical connections
Connecting a central fault message facility
(cont.)
5863679
Installation
Summary of Contents for Vitotronic 11 CC1E