14 Minimum burner runtime
Display
Value
Explanations
Note
Factory settings, according to coding card
... min
14:0 to
14:15
15 Runtime servomotor mod. burner
!
Display
Value
Explanations
Note
Factory settings, according to coding card
... s
15:5 to
15:199
16 Burner offset with start optimisation
Display
Value
Explanations
Burner offset with start optimisation in K (temporary
reduction of the set boiler water temperature after
burner start)
Note
Factory settings, according to coding card
... K
16:0 to
16:15
1A Start optimisation
Display
Value
Explanations
Duration of start optimisation after burner start
Note
Factory settings, according to coding card
... s
1A:0 to
1A:60
1B Time from burner ignition to the start of control
Display
Value
Explanations
Note
Factory settings, according to coding card
... s
1B:0 to
1B:199
Regulation delay adjustable from 1 to 199 s.