55
Display
Explanation
Solar circuit pump max.
ON
Connection at output
sF
at solar control module,
type SM1: Solar circuit pump running at maximum
speed
SM1, output 22
ON
Actuator at output
sS
at solar control module type SM1
EA1 extension, output 1
ON
Contact "P - S" on plug
aBJ
of EA1 extension closed
AM1 extension, output 1
ON
Actuator at output A1 on extension AM1
AM1 extension, output 2
ON
Actuator at output A2 on extension AM1
Information regarding the mixer motor rotational
direction
Return temperature control:
The return temperature must rise when the mixer
opens. If the temperature drops, the motor is turning in
the wrong direction or the mixer set is incorrectly fitted
(observe the mixer installation instructions).
Commissioning
Checking outputs (actuator test)
(cont.)