Coding in the delivered condition
Possible change
79:0
The control unit is not
the fault manager (only
for weather-compen-
sated control units)
79:1
Control unit is fault man-
ager
7b:1
Send time via LON
(only for weather-com-
pensated control units)
7b:0
Do not send time via LON
7F:1
Detached house (only
for weather-compen-
sated control units)
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
80:1
A fault message is dis-
played, providing a fault
is active for at least 5 s
80:0
Immediate fault message
80:2
to
80:199
The minimum fault dura-
tion before a fault mes-
sage is issued is
adjustable from 10 s to
995 s; 1 step = 5 s
81:1
Automatic summer/win-
ter time changeover
81:0
Manual summer/winter
time changeover
81:2
Use of the radio clock re-
ceiver (automatic recog-
nition)
81:3
Accept time via LON
88:0
Temperature displayed
in °C (Celsius)
88:1
Temperature displayed in
°F (Fahrenheit)
8A:175
Do not adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature 21.3 h
90:1
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min
Code 2
(cont.)
50
Coding
5692
731
GB
Summary of Contents for VITODENS 333-F WS3A
Page 113: ...Parts lists cont 113 Parts lists 5692 731 GB ...
Page 114: ...Parts lists cont 114 Parts lists 5692 731 GB ...
Page 115: ...Parts lists cont 115 Parts lists 5692 731 GB ...
Page 116: ...Parts lists cont 116 Parts lists 5692 731 GB ...
Page 117: ...Parts lists cont 117 Parts lists 5692 731 GB ...