Coding in the delivered condition
Possible change
F8:-5
Temperature limit for
terminating the reduced
mode -5 ºC, see exam-
ple on page 103.
Observe the setting of
coding address "A3".
(only for weather-com-
pensated control units)
F8:+10
to
F8:-60
Temperature limit adjus-
table from
+10 to -60 °C
F8:-61
Function disabled
F9:-14
Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 103.
(only for weather-com-
pensated control units)
F9:+10
to
F9:-60
Temperature limit adjus-
table from
+10 to -60 °C
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature, by
20 %. See example on
page 104 (only for
weather-compensated
control units).
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
Fb:30
Duration for raising the
set boiler water tem-
perature or the set flow
temperature (see cod-
ing address "FA")
60 min. See example on
page 104 (only for
weather-compensated
control units).
Fb:0
to
Fb:150
Duration adjustable from
0 to 300 min;
1 step
≙
2 min
Code 2
(cont.)
60
Coding
5692
731
GB
Summary of Contents for VITODENS 333-F WS3A
Page 113: ...Parts lists cont 113 Parts lists 5692 731 GB ...
Page 114: ...Parts lists cont 114 Parts lists 5692 731 GB ...
Page 115: ...Parts lists cont 115 Parts lists 5692 731 GB ...
Page 116: ...Parts lists cont 116 Parts lists 5692 731 GB ...
Page 117: ...Parts lists cont 117 Parts lists 5692 731 GB ...