Coding
Internal circu-
lation pump
Heating circuit
pump
Heating circuit
without mixer
Heating circuit
pump
Heating circuit
with mixer
Cylinder pri-
mary pump
0
Control funct.
Control funct.
Control funct.
Control funct.
1
Control funct.
Control funct.
Control funct.
OFF
2
Control funct.
Control funct.
OFF
Control funct.
3
Control funct.
Control funct.
OFF
OFF
4
Control funct.
OFF
Control funct.
Control funct.
5
Control funct.
OFF
Control funct.
OFF
6
Control funct.
OFF
OFF
Control funct.
7
Control funct.
OFF
OFF
OFF
8
OFF
Control funct.
Control funct.
Control funct.
9
OFF
Control funct.
Control funct.
OFF
10
OFF
Control funct.
OFF
Control funct.
11
OFF
Control funct.
OFF
OFF
12
OFF
OFF
Control funct.
Control funct.
13
OFF
OFF
Control funct.
OFF
14
OFF
OFF
OFF
Control funct.
15
OFF
OFF
OFF
OFF
Coding in the delivered condition
Possible change
Boiler/burner
34:0
Influence of the signal
"External demand" on
the circulation pumps:
All pumps in control
function
34:1
to
34:23
Influence of the signal
"External demand" on the
circulation pumps: see
the following table
Coding
Internal circu-
lation pump
Heating circuit
pump
Heating circuit
without mixer
Heating circuit
pump
Heating circuit
with mixer
Cylinder pri-
mary pump
0
Control funct.
Control funct.
Control funct.
Control funct.
1
Control funct.
Control funct.
Control funct.
OFF
2
Control funct.
Control funct.
OFF
Control funct.
3
Control funct.
Control funct.
OFF
OFF
4
Control funct.
OFF
Control funct.
Control funct.
5
Control funct.
OFF
Control funct.
OFF
6
Control funct.
OFF
OFF
Control funct.
Code 2
(cont.)
46
Coding
5692
731
GB
Summary of Contents for VITODENS 333-F WS3A
Page 113: ...Parts lists cont 113 Parts lists 5692 731 GB ...
Page 114: ...Parts lists cont 114 Parts lists 5692 731 GB ...
Page 115: ...Parts lists cont 115 Parts lists 5692 731 GB ...
Page 116: ...Parts lists cont 116 Parts lists 5692 731 GB ...
Page 117: ...Parts lists cont 117 Parts lists 5692 731 GB ...