Coding in the delivered condition
Possible change
Max. boiler water temp.
06:...
Maximum limit of the
boiler water tempera-
ture, defaulted in °C by
the boiler coding card
06:20
to
06:127
Maximum limit of the boil-
er water temperature
within the ranges de-
faulted by the boiler
Gas type
1E:0
Operation with natural
gas
1E:1
Operation with LPG
Venting/filling
2F:0
Programs disabled
2F:1
Venting program enabled
2F:2
Filling program enabled
Subscriber no.
77:1
LON subscriber number
(only for weather-com-
pensated control units)
77:2
to
77:99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only
once.
Summer econ. A1/M2
A5:5
With heating circuit
pump logic function
(only for weather-com-
pensated control units)
A5:0
Without heating circuit
pump logic function
Min. flow temp. A1/M2
C5:20
Electronic minimum
flow temperature limit
20 °C (only for weather-
compensated control
units)
C5:1
to
C5:127
Minimum limit adjustable
from 10 to 127 °C
Max. flow temp. A1/M2
C6:74
Electronic maximum
flow temperature limit
74 °C (only for weather-
compensated control
units)
C6:10
to
C6:127
Maximum limit adjustable
from 10 to 127 °C
Code 1
(cont.)
42
Coding
5692
731
GB
Summary of Contents for VITODENS 333-F WS3A
Page 113: ...Parts lists cont 113 Parts lists 5692 731 GB ...
Page 114: ...Parts lists cont 114 Parts lists 5692 731 GB ...
Page 115: ...Parts lists cont 115 Parts lists 5692 731 GB ...
Page 116: ...Parts lists cont 116 Parts lists 5692 731 GB ...
Page 117: ...Parts lists cont 117 Parts lists 5692 731 GB ...