77
Heating circuit 3
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Standard room temperature"
4000
200 (
≙
20 °C)
"Reduced room temperature"
4001
200 (
≙
20 °C)
"Remote control"
4003
0
"Heating curve level"
4006
0 (
≙
0 K)
"Heating curve slope"
4007
6 (
≙
0.6)
"Influence room temperature hook-up"
400 A
10
"Room temperature hook-up"
400 B
0
"Max. flow temperature heating circuit"
400E
400 (
≙
40 °C)
"Room temperature in party mode"
4022
160 (
≙
16 °C)
Cooling
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Cooling function"
7100
0
"Cooling circuit"
7101
1
"Set room temperature separate cooling
circuit"
7102
200 (
≙
20 °C)
"Min. flow temperature cooling"
7103
100 (
≙
10 °C)
"Influence room temperature hook-up
cooling circuit"
7104
0
"Ranking room temp sensor separate
cooling circuit"
7106
0
"Cooling curve level"
7110
0 (
≙
0 K)
"Cooling curve slope"
7111
12 (
≙
1.2)
"Remote control cooling circ"
7116
0
"Enable coolant buffer cylinder"
7120
0
"Enable active cooling"
71FE
0
Ventilation
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
"Vitovent enable"
7D00
0
"Enable preheater bank electric"
7D01
0
"Enable reheater bank hydraulic"
7D02
0
"Enable target temperature control"
7D04
0
"Enable humidity sensor"
7D05
0
"Enable CO2 sensor"
7D06
0
"Set extract air temperature"
7D08
200 (
≙
20 °C)
"Flow rate reduced ventilation"
7D0A
120 m
3
/h
"Flow rate nominal ventilation"
7D0B
170 m
3
/h
"Flow rate intensive ventilation"
7D0C
215 m
3
/h
"Min. supply air temperature for bypass"
7D0F
160 (
≙
16 °C)
"CO2 value for raising the flow rate"
7D18
800 ppm
"Humidity value for raising the flow rate"
7D19
65 %
"Interval time frost protection ventila-
tion"
7D1A
15 min
Commissioning/service reports
Control parameter report
(cont.)
5838144
Appendix