55
6. Confirm parameter code:
"7000"
7. Set system scheme:
"6"
Required parameters for components connected on site
Detailed explanations on parameters
"Vitotronic 200" service instructions
Parameters for circulation pumps and other components
Heating circuit pump
Parameter
Setting
"System definition"
Ó
"System scheme 7000"
■
With heating circuit A1/HC1 without
mixer
or
■
With heating circuit M2/HC2 with
mixer
or
■
With heating circuit M3/HC3 with
mixer
Circulation pump for cylinder heating
Parameter
Setting
"System definition"
Ó
"System scheme 7000"
With DHW heating
DHW circulation pump
Parameter
Setting
Extended menu
Ó
"Time program DHW circulation"
Set a time program.
Circulation pump for DHW reheating
Parameter
Setting
"External heat source"
Ó
"Enable external heat source 7B00"
"1"
"Enable external heat source for DHW heating 7B0D"
"1"
Mixer extension kit for heating circuit M3/HC3
Parameter
Setting
"System definition"
Ó
"System scheme 7000"
With heating circuit M3/HC3
Note
Set rotary switch S1 in the extension
kit to "2": See "Mixer extension kit" in-
stallation instructions.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5838144