Heating water buffer cylinder
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
"Enable buffer cylinder/low loss header"
7200
0
"Temp in operating status fixed value for
buffer cyl"
7202
500 (
≙
50 °C)
"Hysteresis temperature heating buffer
cylinder"
7203
50 (
≙
5 K)
"Max. temperature buffer cylinder"
7204
650 (
≙
65 °C)
"Stop optimisation heating buffer cylin-
der"
7205
0
"Temp. limit op. status fixed value for
buffer cylinder"
7208
500 (
≙
50 °C)
"Stop hysteresis, heating water buffer
cylinder"
7209
0 (
≙
0 K)
"Operating mode, fixed value only for
heat demand"
720A
0
Heating circuit 1
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
"Standard room temperature"
2000
200 (
≙
20 °C)
"Reduced room temperature"
2001
160 (
≙
16 °C)
"Remote control"
2003
0
"Room temperature control"
2005
0
"Heating curve level"
2006
0 (
≙
0 K)
"Heating curve slope"
2007
6 (
≙
0.6)
"Influence room temperature hook-up"
200A
10
"Room temperature hook-up"
200B
0
"Max. flow temperature heating circuit"
200E
400 (
≙
40 °C)
"Runtime mixer heating circ"
2015
Do not adjust
"Room temperature in party mode"
2022
200 (
≙
20 °C)
Heating circuit 2
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Standard room temperature"
3000
200 (
≙
20 °C)
"Reduced room temperature"
3001
160 (
≙
16 °C)
"Remote control"
3003
0
"Heating curve level"
3006
0 (
≙
0 K)
"Heating curve slope"
3007
6 (
≙
0.6)
"Influence room temperature hook-up"
300 A
10
"Room temperature hook-up"
300 B
0
"Max. flow temperature heating circuit"
300E
400 (
≙
40 °C)
"Room temperature in party mode"
3022
200 (
≙
20 °C)
Commissioning/service reports
Control parameter report
(cont.)