43
Sensors to be connected on site
Plug
Sensor
Type
F0.1/F0.2
Outside temperature sensor
NTC 10 kΩ
F0.2/F0.3
Radio clock receiver (accessories)
DCF
F4
Buffer temperature sensor, top
NTC 10 kΩ
F6
Cylinder temperature sensor, top
NTC 10 kΩ
F7
Cylinder temperature sensor, bottom
NTC 10 kΩ
F11
Contact humidistat 24 V
–
―
F12
Flow temperature sensor, heating circuit with mixer (M2/HC2)
NTC 10 kΩ
F13
System flow temperature sensor (downstream of heating water buffer cylin-
der)
NTC 10 kΩ
F14
Flow temperature sensor, cooling circuit (heating/cooling circuit without mix-
er A1/HC1 or separate cooling circuit SKK)
NTC 10 kΩ
F16
Room temperature sensor, separate cooling circuit
NTC 10 kΩ
F17
Never connect anything here.
F20
Boiler water temperature sensor, external heat generator
NTC 10 kΩ
F26
Buffer temperature sensor, cooling
NTC 10 kΩ
Sensors connected at the factory (plug X25)
Plug
Sensor
Type
X25.1/X25.2
Flow temperature sensor, primary circuit
Pt500A (PTC)
X25.3/X25.4
Return temperature sensor, primary circuit
Pt500A (PTC)
X25.9/X25.10
Flow temperature sensor, secondary circuit
Pt500A (PTC)
X25.11/X25.12
Return temperature sensor, secondary circuit
Pt500A (PTC)
Plug
Connection
aVG
KM-BUS
Connection of components on site (cores interchangeable). If more than one of the following
devices are to be connected, use a KM-BUS distributor (accessories).
■
Extension kit, mixer for heating circuit with mixer (M3/HC3).
■
Remote control Vitotrol 200-A or Vitotrol 300-B (set the heating circuit assignment at the re-
mote control)
■
EA1 extension, AM1 extension
■
Vitocom 100 communications interface
■
Vitosolic 100/200 solar control units
X24
Connection, LON communication module (plug in on site, see LON communication module in-
stallation instructions)
X31
Coding card slot
Swimming pool heating
Note
■
Swimming pool heating is controlled via EA1 exten-
sion with KM-BUS.
■
Make connections to EA1 extension
only
in accord-
ance with Fig. 33.
■
A filter circuit pump
cannot
be controlled via the heat
pump control unit.
Installation sequence
Electrical connections
(cont.)
5838144
Installation
Summary of Contents for Vitocal 300-G Pro BW 302.D090
Page 90: ...90 5838144...
Page 91: ...91 5838144...