Carry out an operating display adjustment (high flow balancing, if required)
The high flow balancing establishes the existing
(higher) flow rate as the nominal flow rate. For the cor-
responding values for operating mode "water/water
with intermediate circuit" see "Specification" from
page 80.
Note
The high flow balancing can shift the switching point of
the flow switch.
1. Start the appliance with the existing flow rate.
2. Press and hold for around 5 s until LED "9"
flashes.
3. Release .
Fitting the top panel and front panel (closing the heat pump)
See page 49.
Instructing the system user
The system installer should hand the operating instruc-
tions to the system user and instruct the user in oper-
ating the system.
This includes all components installed as accessories,
e.g. remote control units. In addition, the system instal-
ler must make the user aware of the required mainte-
nance work.
Commissioning, inspection, maintenance
Checking the electronic flow switch, type IFM
(cont.)
5838144