61
Terminals
Sensor
Type
37X2
Temperature sensor, cylin-
der, cold water bottom
Connect on site
Cold water option
Pt1000 (PTC)
37X4
Flow temperature sensor,
heating
Cylinder, cold water
Connect on site
Cold water option
Pt1000 (PTC)
Note
All sensor leads and 0-10 V signal leads must be shielded with copper braiding and
have a minimum cross-section of 0.5 mm
2
. Specified lead type: CV.
Sensor
Terminals
Sensor
Type
14X1
Temperature sensor, suc-
tion gas
Heat pump
Wired at the factory
Pt1000 (PTC)
14X2
Temperature sensor
Evaporator inlet
Wired at the factory
Pt1000 (PTC)
14X4
Temperature sensor
Evaporator outlet
Wired at the factory
Pt1000 (PTC)
14X5
Temperature sensor
Condenser inlet
Wired at the factory
Pt1000 (PTC)
14X7
Temperature sensor
Condenser outlet
Wired at the factory
Pt1000 (PTC)
15X0
Temperature sensor
Casing temperature
Wired at the factory
Pt1000 (PTC)
15X3
Pressure sensor
Low pressure
Heat pump
Wired at the factory
TRFG ND9
Installation sequence
Overview of electrical connections
(cont.)
5848 449 GB