64
Type
Heat pump
power sup-
ply (400 V
∼
/
50 Hz)
System com-
ponent power
supply (400 V
∼
/
50 Hz)
Power supply, heat
pump control unit in
the case of power-
OFF with load discon-
nect (400 V
∼
/50 Hz) on
site
Max. cable
length
BW
352.A027/
SA
5 x 35 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A034/
SA
5 x 35 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A056/
SA
5 x 35 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A76/
SA
5 x 50 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A97/
SA
5 x 70 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A114/
SA
5 x 95 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A132/
SA
5 x 95 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
352.A156/
SA
5 x 120 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
353.A172/
SA
5 x 120 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
BW
353.A198/
SA
5 x 150 mm
2
5 x 10 mm
2
5 x 4 mm
2
40 m
Installation sequence
Power supply
(cont.)
5848 449 GB