14
BW 352.A076/SA 963 kg
BW 352.A097/SA 1065 kg
BW 352.A114/SA 1113 kg
BW 352.A132/SA 1209 kg
BW 352.A156/SA 1260 kg
BW 353.A172/SA 1604 kg
BW 353.A198/SA 1678 kg
■ To prevent the transmission of struc-
ture-borne noise, never site the appli-
ance on ceilings with wooden joists
(e.g. in the attic).
■ Level the appliance.
If the adjustable feet are used to com-
pensate for an uneven floor (max.
10 mm), the pressure load on the feet
must be distributed evenly.
■ Observe the minimum room volume to
EN 378.
Note
Additional country-specific regulations
also apply.
Minimum room volume type
BW 352.A027 to BW 353.A198/type
BW 352.A027 SA to
BW 353.A198 SA:
BW 352.A027/SA 16 m
3
BW 352.A034/SA 20 m
3
BW 352.A056/SA 28 m
3
BW 352.A076/SA 40 m
3
BW 352.A097/SA 52 m
3
BW 352.A114/SA 64 m
3
BW 352.A132/SA 76 m
3
BW 352.A156/SA 96 m
3
BW 353.A172/SA 108 m
3
BW 353.A198/SA 144 m
3
■ Observe the required floor area and
minimum clearances (see the follow-
ing chapter).
Minimum clearances
Observe required minimum clearances.
Note
■ Additional strain relief clamps are
required for the power cables if the
clearance behind the heat pump is
greater than 80 mm.
■ Observe clearances required for
installation and service.
■ When siting cascades, observe the
relevant minimum clearances.
A
B
C D
E
700
600
A
Clearance on site subject to instal-
lation and siting
B
Clearance for installation and serv-
ice (e.g. for removing and cleaning
the tubular heat exchanger)
■ Type BW:
≥ 500 mm
■ Type WW:
≥ 2000 mm
Preparing for installation
Siting
(cont.)
5848 449 GB