119
Operation: brine/water
Type BW
Two-stage
352.A
027 /
SA
034 /
SA
056 /
SA
076 /
SA
097 /
SA
Output data
to EN 14511 (B0/W35,
5 K spread)
Rated heating output
kW
27.2
34.3
56.1
76.0
96.9
Cooling capacity
kW
20.8
26.4
43.4
58.8
74.6
Power consumption
kW
6.4
7.9
12.8
17.3
21.9
Coefficient of performance
ε (COP)
4.2
4.4
4.4
4.4
4.41
Brine
(primary circuit)
Content
l
4
5
10
13
18
Nominal flow rate dT 3K
m
3
/h
6.7
8.3
13.7
18.7
23.9
Pressure drop
mbar
150
160
170
190
190
Min. flow rate
*1
m
3
/h
4.5
5.2
8.6
12.0
15.0
Max. flow temperature
°C
25
25
25
25
25
Min. flow temperature at
nominal flow rate
°C
-7
-7
-7
-7
-7
Heating water
(secondary
circuit)
Content
l
4
4.5
8
10
13
Nominal flow rate dT 5 K
m
3
/h
4.8
5.9
9.8
13.2
16.8
Pressure drop
mbar
200
200
200
200
220
Min. flow rate
*1
m
3
/h
2.5
3.0
5.0
6.7
8.5
Max. flow temperature
°C
73
73
73
73
73
Min. flow temperature at
nominal flow rate
°C
30
30
30
30
30
*1
The minimum flow rate results in a lower heat pump output
Specification
5848 449 GB
Service