16
Installation room requirements
!
Please note
The installation room must be dry
and free from the risk of frost.
Ambient temperatures of 0 to
35 ºC must be ensured.
!
Please note
Avoid risk of explosion due to
dust, gases and vapours
in the installation room.
!
Please note
Observe the permissible floor
load.
■ Align the appliance horizon-
tally.
If the adjustable feet are used
to compensate for an uneven
floor (max. 10 mm), the pres-
sure load on the feet must be
distributed evenly.
■ The total weight must be con-
sidered (see table).
Total weight with full DHW cylinder
Type BWT/BWT-
M
Weight in kg
241.A06
480
241.A08
480
241.A10
486
Minimum room volume (to DIN EN 378):
Type BWT/BWT-M
Minimum room volume
in m
3
Floor area in m
2
241.A06
4.7
1.9
241.A08
4.1
1.7
241.A10
4.1
1.7
Installation sequence
Siting the heat pump
5601 598 GB