55
Note
The system must be protected
against frost down to –15 °C.
Viessmann heat transfer medium is a
ready-mixed ethylene glycol-based
medium, for down to –15 °C, contain-
ing inhibitors for corrosion protec-
tion.
3.
Check the connections for possible
leaks. Replace faulty or displaced
gaskets.
Information on setting the primary
pump
Temperature differential between the
primary flow and primary return:
3 K to 5 K.
For this, it may be appropriate to set the
primary pump to a lower stage.
Filling and venting on the secondary side
Unsuitable fill and top-up water increa-
ses the level of deposits and corrosion
and may lead to system damage.
Regarding the quality and amount of
heating water, incl. fill and top-up water,
observe the VDI 2035 [or local regula-
tions].
■ Thoroughly flush the entire heating
system prior to filling it with water.
■ Only use fill water of potable quality.
■ Soften fill water with a hardness above
16.8 °dH (3.0 mol/m
3
), e.g. with the
small softening system for heating
water (see the Viessmann Vitoset
pricelist).
!
Please note
To prevent equipment damage,
protect electrical components on
the shield from escaping liquids.
1.
Open any on-site non-return valves if
installed.
2.
Check the pre-charge pressure of the
expansion vessel (see page 57).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5601 598 GB
Service
Summary of Contents for BWT 241.A Series
Page 20: ...20 aCH 11 10 193C SLP N 224 6 9 Installation sequence Siting the heat pump cont 5601 598 GB...
Page 22: ...22 4x 4x 6x 2x 22 19 21 20 Installation sequence Siting the heat pump cont 5601 598 GB...
Page 23: ...23 4x 23 2x 26 25 24 Installation sequence Siting the heat pump cont 5601 598 GB Installation...
Page 27: ...27 C D BB Installation sequence Siting the heat pump cont 5601 598 GB Installation...
Page 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 598 GB Service...
Page 123: ...123 5601 598 GB...