106
Setting and test values
Set value
Commission-
ing
Frost protection
(brine medium)
°C
– 15
Testing the external heating circuit pumps
Circulation pump type
Circulation pump stage
Overflow valve setting
Primary circuit commissioning
Primary circuit flow temperature
°C
Primary circuit return temperature
°C
Temperature differential ΔT:
Secondary circuit flow temperature =
35 °C when primary circuit flow temperature
= 10 °C
K
3 to 5
Secondary circuit flow temperature =
35 °C when primary circuit flow temperature
= 0 °C
K
2 to 4
Testing the mixer, heat pump and cylinder heating
Checked under the following conditions:
Room temperature
°C
Outside temperature
°C
Temperature
"Cylinder temp. top"
con-
stant?
Yes (±1 K)
Secondary circuit flow temperature
°C
rising
from
to
Temperature differential ΔT
"Flow temp. secondary"
/
"Return temp.
sec."
6 to 8 K
Control parameters report
For a description of parameters, see
separate service instructions, heat pump
Vitotronic 200 control unit.
Commissioning/service reports
Hydraulic parameters report
5601 598 GB
Summary of Contents for BWT 241.A Series
Page 20: ...20 aCH 11 10 193C SLP N 224 6 9 Installation sequence Siting the heat pump cont 5601 598 GB...
Page 22: ...22 4x 4x 6x 2x 22 19 21 20 Installation sequence Siting the heat pump cont 5601 598 GB...
Page 23: ...23 4x 23 2x 26 25 24 Installation sequence Siting the heat pump cont 5601 598 GB Installation...
Page 27: ...27 C D BB Installation sequence Siting the heat pump cont 5601 598 GB Installation...
Page 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 598 GB Service...
Page 123: ...123 5601 598 GB...