142
Operation: brine/water
Type BW
1-stage 301
2-stage 302
A090
A120 A090 A120
A150 A180
A250
Output data
to EN 14511
(B0/W35, 5 K spread)
Rated heating output
kW
93
121
89.4 117.2
150
182
240
Cooling capacity
kW
74.5
96.4
72
93.8
120.1 145.4 191.4
Power consumption
kW
19.5
24.8
18.3
24.4
31.9
39.6
50.4
Coefficient of per-
formance ε (COP)
4.77
4.83
4.88
4.8
4.70
4.60
4.76
Brine
(primary cir-
cuit)
Content
l
33.0
42.0
33.0
42.0
55.2
69.0
89.4
Nominal flow rate to
EN 14511
m³/h
24.5
31.7
24.0
31.3
39.5
47.8
62.9
Min. flow rate (5 K
spread)
m³/h
15.0
19.0
14.5
18.8
24.0
30.0
39.0
Pressure drop
mba
r
120
120
120
120
130
140
180
Max. flow tempera-
ture
°C
20
20
20
20
20
20
20
Min. flow temperature °C
–5
–5
–5
–5
–5
–5
–5
Heating water
(sec-
ondary circuit)
Content
l
22.7
28.7
22.7
28.7
38.7
53.5
57.1
Nominal flow rate to
EN 14511
m³/h
16.0
21.0
15.4
20.3
25.8
31.4
41.4
Min. flow rate (10 K
spread)
m³/h
8.0
10.5
7.8
10.2
12.9
15.7
20.7
Pressure drop (at min.
flow rate)
mbar
100
100
100
100
100
100
120
Flow temperature at
min. primary circuit
flow temperature
–0 °C
°C
55
55
60
60
55
55
55
Flow temperature at
min. primary circuit
flow temperature
+5 °C
°C
60
60
65
65
60
60
60
Specification
Specification type BW 301.A090 to BW 302.A250
5848 164 GB