147
Type WW
1-stage 301
2-stage 302
A125 A155 A125 A155 A200 A250
A300
Electrical values,
heat pump
Rated voltage, com-
pressor
3/PE 400 V/50 Hz
Rated current, com-
pressor (W10/W35)
A
32.7
40.8
31.8
41
25.1
re-
spec-
tively
32.7
re-
spec-
tively
40.8
re-
spec-
tively
Starting current, com-
pressor (with starting
current limiter)
A
< 83 < 130
< 49
re-
spec-
tively
< 56
re-
spec-
tively
< 75
re-
spec-
tively
< 83
re-
spec-
tively
< 130
re-
spec-
tively
Starting current, com-
pressor with stalled
armature
A
287
298
176
re-
spec-
tively
212
re-
spec-
tively
210
re-
spec-
tively
287
re-
spec-
tively
298
re-
spec-
tively
Heat pump MCB/fuse
protection (compres-
sor and consumer)
A
80
100
80
100
125
160
200
Max. operating cur-
rent
A
66
81
60.4
79.8
106
132
162
Electrical values,
control unit
Rated voltage
1/N/PE 230 V/50 Hz
MCB/fuse protection
1 x B16A
MCB/fuse
6.3 AH (slow)/250 V~
Rated output
W
1000
1000 1000
1000
1000
1000
1000
Max. power consump-
tion, stage 1
W
25
25
25
25
25
25
25
Max. power consump-
tion, stage 2
W
20
20
20
20
20
Max. power consump-
tion, stages 1 & 2
W
45
45
45
45
45
Safety category/IP
rating
IP20
IP20
IP20
IP20
IP20
IP20
IP20
Specification
Specification type WW 301.A125 to WW 302.A300
(cont.)
5848 164 GB