Vitodens 100-W, B1HA/B1KA 26 to 125 Combi Installation/Service
Accessing
Electrical Connections
(continued)
Control Connections
Connecting a room thermostat 24VAC
24VAC thermostats require a field supplied switching
relay to terminals 1 and 2 connection
(ie Taco SR501 or Honeywell RA889A-1001)
A
B
Boiler control base
Factory
installed
terminal block
Legend
A
Room thermostat 24VAC (field supplied)
B
Switching relay (field supplied)
Note:
When using the operating methods ‘operation without room temperature thermostat’ or ‘weather compensated operation
without room temperature thermostat’ a jumper must be installed, on terminals 1-2
A
.
Legend
A
Jumper (field supplied)
Without room temperature thermostat
A
Boiler control base
Factory
installed
terminal block
Connecting a room thermostat (dry contacts)
Connect Room Thermostat
(Dry Contact)
A
Boiler control base
Factory
installed
terminal block
Legend
A
Room thermostat dry contact (field supplied)