Observe engineering information.
Technical guides for heat pumps
Cleaning the DHW cylinder
Danger
Uncontrolled escape of DHW or heat transfer
medium can cause scalding and building dam-
age.
Only open DHW and heating water connections
with a depressurised DHW cylinder.
!
Please note
Negative pressure in the DHW cylinder can
cause material damage.
The air vent valve must always be open when
draining the DHW cylinder with a vacuum pump.
!
Please note
Pointed or sharp-edged objects will damage the
DHW cylinder.
Use only suitable cleaning utensils to clean the
cylinder.
!
Please note
Cleaning agents containing hydrochloric acid
attack the DHW cylinder material.
Only use pH-neutral cleaning agents.
1.
8x
B
A
2.
Fig. 50
!
Please note
A short circuit between the magnesium anode
and the internal indirect coil negates the protec-
tive effect of the magnesium anode. This leads
to corrosion damage on the DHW cylinder.
Before connecting the electrical cables, check
the resistance across terminals
A
and
B
. If the
resistance is significantly less than infinity, check
whether the magnesium anode is touching the
internal indirect coil.
Commissioning, inspection, maintenance
Checking expansion vessel and heating circuit pressure