61
Parameters for external functions
Parameter
Setting
External demand
If applicable
"Internal hydraulics"
Ó
"Flow temperature for external demand 730C"
Set flow temperature for external de-
mand
External starting of the compressor; mixer in control mode or OPEN
"System definition"
Ó
"Effect of external demand on heat pump/heating circuits
7014"
"0"
to
"7"
(Observe parameter
"Flow tempera-
ture for external demand 730C"
)
External changeover of the operating status of various system components
"System definition"
Ó
"System components for external changeover 7011"
"0"
to
"127"
"Operating status for external changeover 7012"
"0"
to
"3"
"Duration of external changeover 7013"
"0"
to
"12"
External blocking of compressor and pumps
"System definition"
Ó
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
External blocking of the compressor; mixer in control mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on heat pump/heating circuits 7015"
"0"
to
"8"
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
Parameters for solar DHW heating
Parameter
Setting
"Solar"
Ó
"Type solar control unit 7A00"
"4"
"Flow rate solar circuit for calculating solar yield 7A07"
Specify calculated value from the set
pump rate of the solar circuit pump
and the pressure drop in the solar cir-
cuit in l/h.
Cooling function
Parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
"3"
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"4"
Separate cooling circuit SKK
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5700 582 GB