113
Parameter description
"Vitotronic 200" service instructions
System definition
Parameters
Code
Delivered condition Commission-
ing
Maintenance/
service
"System scheme"
(see chapter "System
scheme")
7000
2
"Temperature differential for calculating
the heating limit"
7003
40 (
≙
4 K)
"Temperature differential for calculating
the cooling limit"
7004
40 (
≙
4 K)
"Swimming pool"
7008
0
"External extension"
7010
0
"System components for external
changeover"
7011
0
"Operating status for external change-
over"
7012
2
"Duration of external changeover"
7013
8 h
"Effect of external demand on heat
pump/heating circuits"
7014
4
"Effect of ext. blocking on heat pump/
heating circuits"
7015
4
"Vitocom 100"
(only type GSM/GSM2)
7017
0
"Effect of external blocking on pumps/
compressor"
701A
0
"Common flow temperature sensor sys-
tem"
701B
0
Compressor
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Enable compressor"
5000
1
"Enable use of compressor stage"
5012
15
"Output compressor stage"
5030
Rated heating output
according to type
plate
"Primary source output"
5043
Do not adjust
Domestic hot water
Parameters
Code
Delivered condition Commission-
ing
Maintenance/
service
"Set DHW temperature"
6000
500 (
≙
50 °C)
"Min. DHW temperature"
6005
100 (
≙
10 °C)
"Max. DHW temperature"
6006
600 (
≙
60 °C)
"Hysteresis DHW temperature heat
pump"
6007
50 (
≙
5 K)
"Hysteresis DHW temperature booster
heater"
6008
100 (
≙
10 K)
"Start optimisation for DHW heating"
6009
0
"Stop optimisation for DHW heating"
600A
0
"Set DHW temperature 2"
600C
600 (
≙
60 °C)
Commissioning/service reports
Control parameters report
5700 582 GB
Appendix